Fuse Size Calculator

Estimate minimum and practical standard fuse current ratings from normal load, design margin, startup inrush, fuse characteristic, and continuous operation. Use the result as an engineering starting point before checking the selected fuse datasheet.

Engineering tool

Fuse Size Calculator

Estimate minimum and practical standard fuse ratings with margin, inrush, and fuse-characteristic context.

Result console

Minimum fuse rating
6.25A
Recommended standard rating
6.3A
Inrush current estimate
10A
Continuous current margin
26%

Fuse selection status

Good

The entered margin meets the common 25% screening target. The selected slow-blow characteristic is better suited to short startup surges, subject to its time-current curve. Because the load is continuous, verify manufacturer derating at the expected ambient temperature.

Fuse protection pathA supply connects through a fuse to a load, showing normal load current, inrush current, and the fuse element.SupplyCircuit voltageFuseFast / Slow-blowLoadIloadNormal current • Inrush currentFuse voltage rating must meet or exceed circuit voltage
The fuse protects the circuit path while tolerating normal operating and permitted transient current.

Formula reference

Fuse Sizing Formulas

The calculated minimum is rounded upward to the next practical standard fuse current rating.

Inrush current = Load current × Inrush multiplierMinimum fuse rating = Load current × (1 + Safety margin)Recommended fuse rating = next standard value above minimumContinuous current margin = (Recommended / Load - 1) × 100%

Variable definitions

Load current
normal operating current
Safety margin
additional continuous-current allowance
Inrush multiplier
startup current divided by normal current

Worked Example

For a 5 A continuous load with 25% margin and a 2× startup surge:

Minimum rating = 5 × 1.25 = 6.25 A. The next practical standard value is 6.3 A. Estimated inrush current is 10 A.

A slow-blow fuse may tolerate the short surge, but its time-current curve and ambient derating must be checked.

Engineering Notes

  • Fuse rating should exceed normal operating current.
  • Slow-blow fuses tolerate short inrush current better than fast-blow fuses.
  • Continuous loads should use derating margin.
  • Fuse voltage rating must meet or exceed circuit voltage.
  • Final fuse selection should check datasheet time-current curves.

Support reference

FAQ

How do I calculate fuse size?

Multiply normal load current by one plus the desired safety margin, then select the next practical standard fuse rating and verify the datasheet time-current curve.

Should fuse rating be higher than load current?

Yes. The fuse must carry normal operating current without nuisance opening while still protecting conductors and equipment under fault conditions.

What is the difference between fast-blow and slow-blow fuse?

Fast-blow fuses open quickly under excess current. Slow-blow fuses tolerate short startup or charging surges before opening under sustained overload.

How much fuse margin should I use?

Twenty-five percent is a common starting point for continuous loads, but ambient temperature, enclosure conditions, inrush, and manufacturer derating rules may require more.